E12 Overload
Fault action
1 Display fault
2 Stop all outputs except water pump
Fault handling
This function is only available for three-phase machines
1 The current is too high. Check whether the condenser ventilation and heat dissipation and water flow are good
2 Is the ambient temperature higher than 43℃ when cooling and higher than 24℃ when heating
3 Check the AC contactor and thermal overload relay
4 Is the compressor reversed? Are the OFL/COM plug and wiring reliable?